IEC61970 16v29a
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC Class Reference

#include <WindContPType3IEC.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU dpmax
 
IEC61970::Base::Domain::PU dprefmax
 
IEC61970::Base::Domain::PU dprefmin
 
IEC61970::Base::Domain::PU dthetamax
 
IEC61970::Base::Domain::PU dthetamaxuvrt
 
IEC61970::Base::Domain::PU kdtd
 
IEC61970::Base::Domain::PU kip
 
IEC61970::Base::Domain::PU kpp
 
IEC61970::Base::Domain::Boolean mpuvrt
 
IEC61970::Base::Domain::PU omegaoffset
 
IEC61970::Base::Domain::PU pdtdmax
 
IEC61970::Base::Domain::Seconds tdvs
 
IEC61970::Base::Domain::PU thetaemin
 
IEC61970::Base::Domain::PU thetauscale
 
IEC61970::Base::Domain::Seconds tomegafiltp3
 
IEC61970::Base::Domain::Seconds tpfiltp3
 
IEC61970::Base::Domain::PU tpord
 
IEC61970::Base::Domain::Seconds tufiltp3
 
IEC61970::Base::Domain::Seconds twref
 
IEC61970::Base::Domain::PU udvs
 
IEC61970::Base::Domain::PU updip
 
IEC61970::Base::Domain::PU wdtd
 
IEC61970::Base::Domain::Float zeta
 
IEC61970::Dynamics::StandardModels::WindDynamics::WindTurbineType3IECWindTurbineType3IEC
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

P control model Type 3.

Reference: IEC Standard 61400-27-1 Section 5.6.5.4.

Member Data Documentation

◆ dpmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dpmax

Maximum wind turbine power ramp rate (dpmax). It is type dependent parameter.

◆ dprefmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dprefmax

Maximum ramp rate of wind turbine reference power (dprefmax). It is project dependent parameter.

◆ dprefmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dprefmin

Minimum ramp rate of wind turbine reference power (dprefmin). It is project dependent parameter.

◆ dthetamax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dthetamax

Ramp limitation of torque, required in some grid codes (dtmax). It is project dependent parameter.

◆ dthetamaxuvrt

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dthetamaxuvrt

Limitation of torque rise rate during UVRT (dthetamaxUVRT). It is project dependent parameter.

◆ kdtd

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kdtd

Gain for active drive train damping (KDTD). It is type dependent parameter.

◆ kip

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kip

PI controller integration parameter (KIp). It is type dependent parameter.

◆ kpp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kpp

PI controller proportional gain (KPp). It is type dependent parameter.

◆ mpuvrt

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::mpuvrt

Enable UVRT power control mode (MpUVRT). true = 1: voltage control false = 0: reactive power control. It is project dependent parameter.

◆ omegaoffset

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::omegaoffset

Offset to reference value that limits controller action during rotor speed changes (omegaoffset). It is case dependent parameter.

◆ pdtdmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::pdtdmax

Maximum active drive train damping power (pDTDmax). It is type dependent parameter.

◆ tdvs

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tdvs

Time delay after deep voltage sags (TDVS). It is project dependent parameter.

◆ thetaemin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::thetaemin

Minimum electrical generator torque (temin). It is type dependent parameter.

◆ thetauscale

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::thetauscale

Voltage scaling factor of reset-torque (tuscale). It is project dependent parameter.

◆ tomegafiltp3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tomegafiltp3

Filter time constant for generator speed measurement (Tomegafiltp3). It is type dependent parameter.

◆ tpfiltp3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tpfiltp3

Filter time constant for power measurement (Tpfiltp3). It is type dependent parameter.

◆ tpord

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tpord

Time constant in power order lag (Tpord). It is type dependent parameter.

◆ tufiltp3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tufiltp3

Filter time constant for voltage measurement (Tufiltp3). It is type dependent parameter.

◆ twref

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::twref

Time constant in speed reference filter (Tomega,ref). It is type dependent parameter.

◆ udvs

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::udvs

Voltage limit for hold UVRT status after deep voltage sags (uDVS). It is project dependent parameter.

◆ updip

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::updip

Voltage dip threshold for P-control (uPdip). Part of turbine control, often different (e.g 0.8) from converter thresholds. It is project dependent parameter.

◆ wdtd

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::wdtd

Active drive train damping frequency (omegaDTD). It can be calculated from two mass model parameters. It is type dependent parameter.

◆ WindTurbineType3IEC

IEC61970::Dynamics::StandardModels::WindDynamics::WindTurbineType3IEC* IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::WindTurbineType3IEC

Wind turbine type 3 model with which this Wind control P type 3 model is associated.

◆ zeta

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::zeta

Coefficient for active drive train damping (zeta). It is type dependent parameter.


The documentation for this class was generated from the following files: