#include <UnderexcLimIEEE2.h>
The class represents the Type UEL2 which has either a straight-line or multi- segment characteristic when plotted in terms of machine reactive power output vs. real power output.
Reference: IEEE UEL2 421.5-2005 Section 10.2. (Limit characteristic lookup table shown in Figure 10.4 (p 32) of the standard).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::k1 |
UEL terminal voltage exponent applied to real power input to UEL limit look-up table (k1). Typical Value = 2.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::k2 |
UEL terminal voltage exponent applied to reactive power output from UEL limit look-up table (k2). Typical Value = 2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::kfb |
Gain associated with optional integrator feedback input signal to UEL (KFB). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::kuf |
UEL excitation system stabilizer gain (KUF). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::kui |
UEL integral gain (KUI). Typical Value = 0.5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::kul |
UEL proportional gain (KUL). Typical Value = 0.8.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p0 |
Real power values for endpoints (P0). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p1 |
Real power values for endpoints (P1). Typical Value = 0.3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p10 |
Real power values for endpoints (P10).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p2 |
Real power values for endpoints (P2). Typical Value = 0.6.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p3 |
Real power values for endpoints (P3). Typical Value = 0.9.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p4 |
Real power values for endpoints (P4). Typical Value = 1.02.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p5 |
Real power values for endpoints (P5).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p6 |
Real power values for endpoints (P6).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p7 |
Real power values for endpoints (P7).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p8 |
Real power values for endpoints (P8).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::p9 |
Real power values for endpoints (P9).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q0 |
Reactive power values for endpoints (Q0). Typical Value = -0.31.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q1 |
Reactive power values for endpoints (Q1). Typical Value = -0.31.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q10 |
Reactive power values for endpoints (Q10).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q2 |
Reactive power values for endpoints (Q2). Typical Value = -0.28.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q3 |
Reactive power values for endpoints (Q3). Typical Value = -0.21.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q4 |
Reactive power values for endpoints (Q4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q5 |
Reactive power values for endpoints (Q5).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q6 |
Reactive power values for endpoints (Q6).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q7 |
Reactive power values for endpoints (Q7).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q8 |
Reactive power values for endpoints (Q8).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::q9 |
Reactive power values for endpoints (Q9).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tu1 |
UEL lead time constant (TU1). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tu2 |
UEL lag time constant (TU2). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tu3 |
UEL lead time constant (TU3). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tu4 |
UEL lag time constant (TU4). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tul |
Time constant associated with optional integrator feedback input signal to UEL (TUL). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tup |
Real power filter time constant (TUP). Typical Value = 5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tuq |
Reactive power filter time constant (TUQ). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::tuv |
Voltage filter time constant (TUV). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::vuimax |
UEL integrator output maximum limit (VUIMAX). Typical Value = 0.25.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::vuimin |
UEL integrator output minimum limit (VUIMIN). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::vulmax |
UEL output maximum limit (VULMAX). Typical Value = 0.25.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE2::vulmin |
UEL output minimum limit (VULMIN). Typical Value = 0.