#include <UnderexcLimIEEE1.h>


The class represents the Type UEL1 model which has a circular limit boundary when plotted in terms of machine reactive power vs. real power output.
Reference: IEEE UEL1 421.5-2005 Section 10.1.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::kuc |
UEL center setting (KUC). Typical Value = 1.38.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::kuf |
UEL excitation system stabilizer gain (KUF). Typical Value = 3.3.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::kui |
UEL integral gain (KUI). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::kul |
UEL proportional gain (KUL). Typical Value = 100.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::kur |
UEL radius setting (KUR). Typical Value = 1.95.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::tu1 |
UEL lead time constant (TU1). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::tu2 |
UEL lag time constant (TU2). Typical Value = 0.05.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::tu3 |
UEL lead time constant (TU3). Typical Value = 0.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::tu4 |
UEL lag time constant (TU4). Typical Value = 0.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::vucmax |
UEL maximum limit for operating point phasor magnitude (VUCMAX). Typical Value = 5.8.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::vuimax |
UEL integrator output maximum limit (VUIMAX).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::vuimin |
UEL integrator output minimum limit (VUIMIN).
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::vulmax |
UEL output maximum limit (VULMAX). Typical Value = 18.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::vulmin |
UEL output minimum limit (VULMIN). Typical Value = -18.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::UnderexcitationLimiterDynamics::UnderexcLimIEEE1::vurmax |
UEL maximum limit for radius phasor magnitude (VURMAX). Typical Value = 5.8.