Simplified model of boiler and steam turbine with PID governor.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::chc |
Control valves rate closing limit (Chc). Unit = PU/sec. Typical Value = -3.3.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::cho |
Control valves rate opening limit (Cho). Unit = PU/sec. Typical Value = 0.17.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::cic |
Intercept valves rate closing limit (Cic). Typical Value = -2.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::cio |
Intercept valves rate opening limit (Cio). Typical Value = 0.123.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::db1 |
Dead band of the frequency corrector (db1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::db2 |
Dead band of the speed governor (db2). Typical Value = 0.0004.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::hhpmax |
Maximum control valve position (Hhpmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::ke |
Gain of the power controller (Ke). Typical Value = 0.65.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::kfcor |
Gain of the frequency corrector (Kfcor). Typical Value = 20.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::khp |
Fraction of total turbine output generated by HP part (Khp). Typical Value = 0. 277.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::klp |
Fraction of total turbine output generated by HP part (Klp). Typical Value = 0. 723.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::kwcor |
Gain of the speed governor (Kwcor). Typical Value = 20.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::mwbase |
Base for power values (MWbase) (>0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::pmax |
Maximal active power of the turbine (Pmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::prhmax |
Maximum low pressure limit (Prhmax). Typical Value = 1.4.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::simx |
Intercept valves transfer limit (Simx). Typical Value = 0.425.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tb |
Boiler time constant (Tb). Typical Value = 100.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tdp |
Derivative time constant of the power controller (Tdp). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::ten |
Electro hydraulic transducer (Ten). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tf |
Frequency transducer time constant (Tf). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tfp |
Time constant of the power controller (Tfp). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::thp |
High pressure (HP) time constant of the turbine (Thp). Typical Value = 0.31.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tip |
Integral time constant of the power controller (Tip). Typical Value = 2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tlp |
Low pressure(LP) time constant of the turbine (Tlp). Typical Value = 0.45.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tp |
Power transducer time constant (Tp). Typical Value = 0.07.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::trh |
Reheater time constant of the turbine (Trh). Typical Value = 8.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tvhp |
Control valves servo time constant (Tvhp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tvip |
Intercept valves servo time constant (Tvip). Typical Value = 0.15.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::tw |
Speed transducer time constant (Tw). Typical Value = 0.02.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wfmax |
Upper limit for frequency correction (Wfmax). Typical Value = 0.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wfmin |
Lower limit for frequency correction (Wfmin). Typical Value = -0.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wmax1 |
Emergency speed control lower limit (wmax1). Typical Value = 1.025.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wmax2 |
Emergency speed control upper limit (wmax2). Typical Value = 1.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wwmax |
Upper limit for the speed governor (Wwmax). Typical Value = 0.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamEU::wwmin |
Lower limit for the speed governor frequency correction (Wwmin). Typical Value = -1.