#include <GovSteamCC.h>
Cross compound turbine governor model.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::dhp |
HP damping factor (Dhp). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::dlp |
LP damping factor (Dlp). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::fhp |
Fraction of HP power ahead of reheater (Fhp). Typical Value = 0.3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::flp |
Fraction of LP power ahead of reheater (Flp). Typical Value = 0.7.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::mwbase |
Base for power values (MWbase) (>0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::pmaxhp |
Maximum HP value position (Pmaxhp). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::pmaxlp |
Maximum LP value position (Pmaxlp). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::rhp |
HP governor droop (Rhp). Typical Value = 0.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::rlp |
LP governor droop (Rlp). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t1hp |
HP governor time constant (T1hp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t1lp |
LP governor time constant (T1lp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t3hp |
HP turbine time constant (T3hp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t3lp |
LP turbine time constant (T3lp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t4hp |
HP turbine time constant (T4hp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t4lp |
LP turbine time constant (T4lp). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t5hp |
HP reheater time constant (T5hp). Typical Value = 10.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovSteamCC::t5lp |
LP reheater time constant (T5lp). Typical Value = 10.