#include <GovHydroR.h>
Fourth order lead-lag governor and hydro turbine.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::at |
Turbine gain (At). Typical Value = 1.2.
IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::db1 |
Intentional dead-band width (db1). Unit = Hz. Typical Value = 0.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::db2 |
Unintentional dead-band (db2). Unit = MW. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::dturb |
Turbine damping factor (Dturb). Typical Value = 0.2.
IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::eps |
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gmax |
Maximum governor output (Gmax). Typical Value = 1.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gmin |
Minimum governor output (Gmin). Typical Value = -0.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv1 |
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv2 |
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv3 |
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv4 |
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv5 |
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::gv6 |
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::h0 |
Turbine nominal head (H0). Typical Value = 1.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::inputSignal |
Input signal switch (Flag). true = Pe input is used false = feedback is received from CV. Flag is normally dependent on Tt. If Tf is zero, Flag is set to false. If Tf is not zero, Flag is set to true. Typical Value = true.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::kg |
Gate servo gain (Kg). Typical Value = 2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::ki |
Integral gain (Ki). Typical Value = 0.5.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::mwbase |
Base for power values (MWbase) (>0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv1 |
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv2 |
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv3 |
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv4 |
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv5 |
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pgv6 |
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pmax |
Maximum gate opening, PU of MWbase (Pmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::pmin |
Minimum gate opening, PU of MWbase (Pmin). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::qnl |
No-load turbine flow at nominal head (Qnl). Typical Value = 0.08.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::r |
Steady-state droop (R). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t1 |
Lead time constant 1 (T1). Typical Value = 1.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t2 |
Lag time constant 1 (T2). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t3 |
Lead time constant 2 (T3). Typical Value = 1.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t4 |
Lag time constant 2 (T4). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t5 |
Lead time constant 3 (T5). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t6 |
Lag time constant 3 (T6). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t7 |
Lead time constant 4 (T7). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::t8 |
Lag time constant 4 (T8). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::td |
Input filter time constant (Td). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::tp |
Gate servo time constant (Tp). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::tt |
Power feedback time constant (Tt). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::tw |
Water inertia time constant (Tw). Typical Value = 1.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::velcl |
Maximum gate closing velocity (Velcl). Unit = PU/sec. Typical Value = -0.2.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroR::velop |
Maximum gate opening velocity (Velop). Unit = PU/sec. Typical Value = 0.2.