#include <GovHydro2.h>
IEEE hydro turbine governor model represents plants with straightforward penstock configurations and hydraulic-dashpot governors.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::aturb |
Turbine numerator multiplier (Aturb). Typical Value = -1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::bturb |
Turbine denominator multiplier (Bturb). Typical Value = 0.5.
IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::db1 |
Intentional deadband width (db1). Unit = Hz. Typical Value = 0.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::db2 |
Unintentional deadband (db2). Unit = MW. Typical Value = 0.
IEC61970::Base::Domain::Frequency IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::eps |
Intentional db hysteresis (eps). Unit = Hz. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv1 |
Nonlinear gain point 1, PU gv (Gv1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv2 |
Nonlinear gain point 2, PU gv (Gv2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv3 |
Nonlinear gain point 3, PU gv (Gv3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv4 |
Nonlinear gain point 4, PU gv (Gv4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv5 |
Nonlinear gain point 5, PU gv (Gv5). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::gv6 |
Nonlinear gain point 6, PU gv (Gv6). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::kturb |
Turbine gain (Kturb). Typical Value = 1.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::mwbase |
Base for power values (MWbase) (> 0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv1 |
Nonlinear gain point 1, PU power (Pgv1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv2 |
Nonlinear gain point 2, PU power (Pgv2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv3 |
Nonlinear gain point 3, PU power (Pgv3). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv4 |
Nonlinear gain point 4, PU power (Pgv4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv5 |
Nonlinear gain point 5, PU power (Pgv5). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pgv6 |
Nonlinear gain point 6, PU power (Pgv6). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pmax |
Maximum gate opening (Pmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::pmin |
Minimum gate opening; (Pmin). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::rperm |
Permanent droop (Rperm). Typical Value = 0.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::rtemp |
Temporary droop (Rtemp). Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tg |
Gate servo time constant (Tg). Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tp |
Pilot servo valve time constant (Tp). Typical Value = 0.03.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tr |
Dashpot time constant (Tr). Typical Value = 12.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::tw |
Water inertia time constant (Tw). Typical Value = 2.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::uc |
Maximum gate closing velocity (Uc) (<0). Unit = PU/sec. Typical Value = -0.1.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro2::uo |
Maximum gate opening velocity (Uo). Unit = PU/sec. Typical Value = 0.1.