#include <GovHydro1.h>
Basic Hydro turbine governor model.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::at |
Turbine gain (At) (>0). Typical Value = 1.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::dturb |
Turbine damping factor (Dturb) (>=0). Typical Value = 0.5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::gmax |
Maximum gate opening (Gmax) (>0). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::gmin |
Minimum gate opening (Gmin) (>=0). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::hdam |
Turbine nominal head (hdam). Typical Value = 1.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::mwbase |
Base for power values (MWbase) (> 0). Unit = MW.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::qnl |
No-load flow at nominal head (qnl) (>=0). Typical Value = 0.08.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::rperm |
Permanent droop (R) (>0). Typical Value = 0.04.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::rtemp |
Temporary droop (r) (>R). Typical Value = 0.3.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tf |
Filter time constant (Tf) (>0). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tg |
Gate servo time constant (Tg) (>0). Typical Value = 0.5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tr |
Washout time constant (Tr) (>0). Typical Value = 5.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::tw |
Water inertia time constant (Tw) (>0). Typical Value = 1.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydro1::velm |
Maximum gate velocity (Vlem) (>0). Typical Value = 0.2.