IEC61970::Base::Domain::Float a
 
IEC61970::Base::Domain::PU af1
 
IEC61970::Base::Domain::PU af2
 
IEC61970::Base::Domain::Float b
 
IEC61970::Base::Domain::PU bf1
 
IEC61970::Base::Domain::PU bf2
 
IEC61970::Base::Domain::Float c
 
IEC61970::Base::Domain::PU cf2
 
IEC61970::Base::Domain::Seconds ecr
 
IEC61970::Base::Domain::Seconds etd
 
IEC61970::Base::Domain::PU k3
 
IEC61970::Base::Domain::PU k4
 
IEC61970::Base::Domain::PU k5
 
IEC61970::Base::Domain::PU k6
 
IEC61970::Base::Domain::PU kd
 
IEC61970::Base::Domain::PU kdroop
 
IEC61970::Base::Domain::PU kf
 
IEC61970::Base::Domain::PU ki
 
IEC61970::Base::Domain::PU kp
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::Seconds t
 
IEC61970::Base::Domain::Seconds t3
 
IEC61970::Base::Domain::Seconds t4
 
IEC61970::Base::Domain::Seconds t5
 
IEC61970::Base::Domain::Temperature tc
 
IEC61970::Base::Domain::Seconds tcd
 
IEC61970::Base::Domain::Seconds td
 
IEC61970::Base::Domain::Seconds tf
 
IEC61970::Base::Domain::PU tmax
 
IEC61970::Base::Domain::PU tmin
 
IEC61970::Base::Domain::Temperature tr
 
IEC61970::Base::Domain::ActivePower trate
 
IEC61970::Base::Domain::Seconds tt
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Woodward Gas turbine governor model.

Member Data Documentation

◆ a

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::a

Valve positioner (A).

◆ af1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::af1

Exhaust temperature Parameter (Af1).

◆ af2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::af2

Coefficient equal to 0.5(1-speed) (Af2).

◆ b

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::b

Valve positioner (B).

◆ bf1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::bf1

(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0.55 to 0.65 x Tr.

◆ bf2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::bf2

Turbine Torque Coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2).

◆ c

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::c

Valve positioner (C).

◆ cf2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::cf2

Coefficient defining fuel flow where power output is 0% (Cf2). Synchronous but no output. Typically 0.23 x Khhv (23% fuel flow).

◆ ecr

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::ecr

Combustion reaction time delay (Ecr).

◆ etd

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::etd

Turbine and exhaust delay (Etd).

◆ k3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k3

Ratio of Fuel Adjustment (K3).

◆ k4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k4

Gain of radiation shield (K4).

◆ k5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k5

Gain of radiation shield (K5).

◆ k6

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k6

Minimum fuel flow (K6).

◆ kd

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kd

Drop Governor Gain (Kd).

◆ kdroop

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kdroop

(Kdroop).

◆ kf

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kf

Fuel system feedback (Kf).

◆ ki

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::ki

Isochronous Governor Gain (Ki).

◆ kp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kp

PID Proportional gain (Kp).

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::mwbase

Base for power values (MWbase) (> 0). Unit = MW.

◆ t

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t

Fuel Control Time Constant (T).

◆ t3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t3

Radiation shield time constant (T3).

◆ t4

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t4

Thermocouple time constant (T4).

◆ t5

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t5

Temperature control time constant (T5).

◆ tc

IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tc

Temperature control (Tc).

◆ tcd

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tcd

Compressor discharge time constant (Tcd).

◆ td

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::td

Power transducer time constant (Td).

◆ tf

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tf

Fuel system time constant (Tf).

◆ tmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tmax

Maximum Turbine limit (Tmax).

◆ tmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tmin

Minimum Turbine limit (Tmin).

◆ tr

IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tr

Rated temperature (Tr).

◆ trate

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::trate

Turbine rating (Trate). Unit = MW.

◆ tt

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tt

Temperature controller integration rate (Tt).