#include <GovGASTWD.h>
Woodward Gas turbine governor model.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::a |
Valve positioner (A).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::af1 |
Exhaust temperature Parameter (Af1).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::af2 |
Coefficient equal to 0.5(1-speed) (Af2).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::b |
Valve positioner (B).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::bf1 |
(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0.55 to 0.65 x Tr.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::bf2 |
Turbine Torque Coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::c |
Valve positioner (C).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::cf2 |
Coefficient defining fuel flow where power output is 0% (Cf2). Synchronous but no output. Typically 0.23 x Khhv (23% fuel flow).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::ecr |
Combustion reaction time delay (Ecr).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::etd |
Turbine and exhaust delay (Etd).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k3 |
Ratio of Fuel Adjustment (K3).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k4 |
Gain of radiation shield (K4).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k5 |
Gain of radiation shield (K5).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::k6 |
Minimum fuel flow (K6).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kd |
Drop Governor Gain (Kd).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kdroop |
(Kdroop).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kf |
Fuel system feedback (Kf).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::ki |
Isochronous Governor Gain (Ki).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::kp |
PID Proportional gain (Kp).
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::mwbase |
Base for power values (MWbase) (> 0). Unit = MW.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t |
Fuel Control Time Constant (T).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t3 |
Radiation shield time constant (T3).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t4 |
Thermocouple time constant (T4).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::t5 |
Temperature control time constant (T5).
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tc |
Temperature control (Tc).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tcd |
Compressor discharge time constant (Tcd).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::td |
Power transducer time constant (Td).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tf |
Fuel system time constant (Tf).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tmax |
Maximum Turbine limit (Tmax).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tmin |
Minimum Turbine limit (Tmin).
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tr |
Rated temperature (Tr).
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::trate |
Turbine rating (Trate). Unit = MW.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGASTWD::tt |
Temperature controller integration rate (Tt).