IEC61970 16v29a
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4 Class Reference

#include <GovGAST4.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU bp
 
IEC61970::Base::Domain::PU ktm
 
IEC61970::Base::Domain::PU mnef
 
IEC61970::Base::Domain::PU mxef
 
IEC61970::Base::Domain::PU rymn
 
IEC61970::Base::Domain::PU rymx
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::Seconds tcm
 
IEC61970::Base::Domain::Seconds tm
 
IEC61970::Base::Domain::Seconds tv
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Generic turbogas.

Member Data Documentation

◆ bp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::bp

Droop (bp). Typical Value = 0.05.

◆ ktm

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::ktm

Compressor gain (Ktm). Typical Value = 0.

◆ mnef

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::mnef

Fuel flow maximum negative error value (MNEF). Typical Value = -0. 05.

◆ mxef

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::mxef

Fuel flow maximum positive error value (MXEF). Typical Value = 0.05.

◆ rymn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::rymn

Minimum valve opening (RYMN). Typical Value = 0.

◆ rymx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::rymx

Maximum valve opening (RYMX). Typical Value = 1.1.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::ta

Maximum gate opening velocity (TA). Typical Value = 3.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::tc

Maximum gate closing velocity (Tc). Typical Value = 0.5.

◆ tcm

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::tcm

Fuel control time constant (Tcm). Typical Value = 0.1.

◆ tm

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::tm

Compressor discharge volume time constant (Tm). Typical Value = 0.2.

◆ tv

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST4::tv

Time constant of fuel valve positioner (Ty). Typical Value = 0.1.


The documentation for this class was generated from the following files: