#include <GovGAST2.h>
Gas turbine model.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::a |
Valve positioner (A).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::af1 |
Exhaust temperature Parameter (Af1). Unit = per unit temperature. Based on temperature in degrees C.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::af2 |
Coefficient equal to 0.5(1-speed) (Af2).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::b |
Valve positioner (B).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::bf1 |
(Bf1). Bf1 = E(1-w) where E (speed sensitivity coefficient) is 0.55 to 0.65 x Tr. Unit = per unit temperature. Based on temperature in degrees C.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::bf2 |
Turbine Torque Coefficient Khhv (depends on heating value of fuel stream in combustion chamber) (Bf2).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::c |
Valve positioner (C).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::cf2 |
Coefficient defining fuel flow where power output is 0% (Cf2). Synchronous but no output. Typically 0.23 x Khhv (23% fuel flow).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::ecr |
Combustion reaction time delay (Ecr).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::etd |
Turbine and exhaust delay (Etd).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::k3 |
Ratio of Fuel Adjustment (K3).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::k4 |
Gain of radiation shield (K4).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::k5 |
Gain of radiation shield (K5).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::k6 |
Minimum fuel flow (K6).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::kf |
Fuel system feedback (Kf).
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::mwbase |
Base for power values (MWbase) (> 0). Unit = MW.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::t |
Fuel Control Time Constant (T).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::t3 |
Radiation shield time constant (T3).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::t4 |
Thermocouple time constant (T4).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::t5 |
Temperature control time constant (T5).
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tc |
Temperature control (Tc). Unit = °F or °C depending on constants Af1 and Bf1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tcd |
Compressor discharge time constant (Tcd).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tf |
Fuel system time constant (Tf).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tmax |
Maximum Turbine limit (Tmax).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tmin |
Minimum Turbine limit (Tmin).
IEC61970::Base::Domain::Temperature IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tr |
Rated temperature (Tr). Unit = °C depending on parameters Af1 and Bf1.
IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::trate |
Turbine rating (Trate). Unit = MW.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::tt |
Temperature controller integration rate (Tt).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::w |
Governor gain (1/droop) on turbine rating (W).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::x |
Governor lead time constant (X).
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::y |
Governor lag time constant (Y) (>0).
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovGAST2::z |
Governor mode (Z). true = Droop false = ISO.