#include <PssSK.h>


PSS Slovakian type – three inputs.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::k1 |
Gain P (K1). Typical Value = -0.3.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::k2 |
Gain fe (K2). Typical Value = -0.15.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::k3 |
Gain If (K3). Typical Value = 10.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t1 |
Denominator time constant (T1). Typical Value = 0.3.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t2 |
Filter time constant (T2). Typical Value = 0.35.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t3 |
Denominator time constant (T3). Typical Value = 0.22.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t4 |
Filter time constant (T4). Typical Value = 0.02.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t5 |
Denominator time constant (T5). Typical Value = 0.02.
| IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::t6 |
Filter time constant (T6). Typical Value = 0.02.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::vsmax |
Stabilizer output max limit (Vsmax). Typical Value = 0.4.
| IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::PssSK::vsmin |
Stabilizer output min limit (Vsmin). Typical Value = -0.4.
1.8.13