#include <Pss2B.h>
Modified IEEE PSS2B Model. Extra lead/lag (or rate) block added at end (up to 4 lead/lags total).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::a |
Numerator constant (a). Typical Value = 1.
IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::inputSignal1Type = IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind::_undef |
Type of input signal #1. Typical Value = rotorSpeed.
IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::inputSignal2Type = IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::InputSignalKind::_undef |
Type of input signal #2. Typical Value = generatorElectricalPower.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::ks1 |
Stabilizer gain (Ks1). Typical Value = 12.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::ks2 |
Gain on signal #2 (Ks2). Typical Value = 0.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::ks3 |
Gain on signal #2 input before ramp-tracking filter (Ks3). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::ks4 |
Gain on signal #2 input after ramp-tracking filter (Ks4). Typical Value = 1.
IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::m |
Denominator order of ramp tracking filter (M). Typical Value = 5.
IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::n |
Order of ramp tracking filter (N). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t1 |
Lead/lag time constant (T1). Typical Value = 0.12.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t10 |
Lead/lag time constant (T10). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t11 |
Lead/lag time constant (T11). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t2 |
Lead/lag time constant (T2). Typical Value = 0.02.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t3 |
Lead/lag time constant (T3). Typical Value = 0.3.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t4 |
Lead/lag time constant (T4). Typical Value = 0.02.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t6 |
Time constant on signal #1 (T6). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t7 |
Time constant on signal #2 (T7). Typical Value = 2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t8 |
Lead of ramp tracking filter (T8). Typical Value = 0.2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::t9 |
Lag of ramp tracking filter (T9). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::ta |
Lead constant (Ta). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::tb |
Lag time constant (Tb). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::tw1 |
First washout on signal #1 (Tw1). Typical Value = 2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::tw2 |
Second washout on signal #1 (Tw2). Typical Value = 2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::tw3 |
First washout on signal #2 (Tw3). Typical Value = 2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::tw4 |
Second washout on signal #2 (Tw4). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::vsi1max |
Input signal #1 max limit (Vsi1max). Typical Value = 2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::vsi1min |
Input signal #1 min limit (Vsi1min). Typical Value = -2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::vsi2max |
Input signal #2 max limit (Vsi2max). Typical Value = 2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::vsi2min |
Input signal #2 min limit (Vsi2min). Typical Value = -2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::vstmax |
Stabilizer output max limit (Vstmax). Typical Value = 0.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PowerSystemStabilizerDynamics::Pss2B::vstmin |
Stabilizer output min limit (Vstmin). Typical Value = -0.1.