#include <OverexcLimX2.h>
Field Voltage or Current overexcitation limiter designed to protect the generator field of an AC machine with automatic excitation control from overheating due to prolonged overexcitation.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efd1 |
Low voltage or current point on the inverse time characteristic (EFD1). Typical Value = 1.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efd2 |
Mid voltage or current point on the inverse time characteristic (EFD2). Typical Value = 1.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efd3 |
High voltage or current point on the inverse time characteristic (EFD3). Typical Value = 1.5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efddes |
Desired field voltage if m=F or field current if m=T (EFDDES). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::efdrated |
Rated field voltage if m=F or field current if m=T (EFDRATED). Typical Value = 1.05.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::kmx |
Gain (KMX). Typical Value = 0.002.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::m |
(m). true = IFD limiting false = EFD limiting.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::t1 |
Time to trip the exciter at the low voltage or current point on the inverse time characteristic (TIME1). Typical Value = 120.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::t2 |
Time to trip the exciter at the mid voltage or current point on the inverse time characteristic (TIME2). Typical Value = 40.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::t3 |
Time to trip the exciter at the high voltage or current point on the inverse time characteristic (TIME3). Typical Value = 15.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLimX2::vlow |
Low voltage limit (VLOW) (>0).