IEC61970 16v29a
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2 Class Reference

#include <OverexcLim2.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU ifdlim
 
IEC61970::Base::Domain::PU koi
 
IEC61970::Base::Domain::PU voimax
 
IEC61970::Base::Domain::PU voimin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcitationLimiterDynamics
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamicsExcitationSystemDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Different from LimIEEEOEL, LimOEL2 has a fixed pickup threshold and reduces the excitation set-point by mean of non-windup integral regulator. Irated is the rated machine excitation current (calculated from nameplate conditions: Vnom, Pnom, CosPhinom).

Member Data Documentation

◆ ifdlim

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::ifdlim

Limit value of rated field current (IFDLIM). Typical Value = 1.05.

◆ koi

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::koi

Gain Over excitation limiter (KOI). Typical Value = 0.1.

◆ voimax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::voimax

Maximum error signal (VOIMAX). Typical Value = 0.

◆ voimin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::OverexcitationLimiterDynamics::OverexcLim2::voimin

Minimum error signal (VOIMIN). Typical Value = -9999.


The documentation for this class was generated from the following files: