#include <ExcST7B.h>
Modified IEEE ST7B static excitation system without stator current limiter (SCL) and current compensator (DROOP) inputs.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::kh |
High-value gate feedback gain (Kh). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::kia |
Voltage regulator integral gain (Kia). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::kl |
Low-value gate feedback gain (Kl). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::kpa |
Voltage regulator proportional gain (Kpa). Typical Value = 40.
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7BOELselectorKind IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::oelin = IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7BOELselectorKind::_undef |
OEL input selector (OELin). Typical Value = noOELinput.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::tb |
Regulator lag time constant (Tb). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::tc |
Regulator lead time constant (Tc). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::tf |
Excitation control system stabilizer time constant (Tf). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::tg |
Feedback time constant of inner loop field voltage regulator (Tg). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::tia |
Feedback time constant (Tia). Typical Value = 3.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::ts |
Rectifier firing time constant (Ts). Typical Value = 0.
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7BUELselectorKind IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::uelin = IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7BUELselectorKind::_undef |
UEL input selector (UELin). Typical Value = noUELinput.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::vmax |
Maximum voltage reference signal (Vmax). Typical Value = 1.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::vmin |
Minimum voltage reference signal (Vmin). Typical Value = 0.9.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::vrmax |
Maximum voltage regulator output (Vrmax). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST7B::vrmin |
Minimum voltage regulator output (Vrmin). Typical Value = -4.5.