Public Attributes

IEC61970::Base::Domain::PU efdmax
 
IEC61970::Base::Domain::PU kc
 
IEC61970::Base::Domain::PU kg
 
IEC61970::Base::Domain::PU ki
 
IEC61970::Base::Domain::PU kj
 
IEC61970::Base::Domain::PU km
 
IEC61970::Base::Domain::PU kp
 
IEC61970::Base::Domain::PU ks
 
IEC61970::Base::Domain::PU ks1
 
IEC61970::Base::Domain::Seconds tb
 
IEC61970::Base::Domain::Seconds tc
 
IEC61970::Base::Domain::AngleDegrees thetap
 
IEC61970::Base::Domain::Seconds tm
 
IEC61970::Base::Domain::PU vbmax
 
IEC61970::Base::Domain::PU vgmax
 
IEC61970::Base::Domain::PU vimax
 
IEC61970::Base::Domain::PU vimin
 
IEC61970::Base::Domain::PU vrmax
 
IEC61970::Base::Domain::PU vrmin
 
IEC61970::Base::Domain::PU xl
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Modified IEEE ST3A static excitation system with added speed multiplier.

Member Data Documentation

◆ efdmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::efdmax

Maximum AVR output (Efdmax). Typical Value = 6.9.

◆ kc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::kc

Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 1.1.

◆ kg

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::kg

Feedback gain constant of the inner loop field regulator (Kg). Typical Value = 1.

◆ ki

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::ki

Potential circuit gain coefficient (Ki). Typical Value = 4.83.

◆ kj

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::kj

AVR gain (Kj). Typical Value = 200.

◆ km

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::km

Forward gain constant of the inner loop field regulator (Km). Typical Value = 7.04.

◆ kp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::kp

Potential source gain (Kp) (>0). Typical Value = 4.37.

◆ ks

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::ks

Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0.

◆ ks1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::ks1

Coefficient to allow different usage of the model-speed coefficient (Ks1). Typical Value = 0.

◆ tb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::tb

Voltage regulator time constant (Tb). Typical Value = 6.67.

◆ tc

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::tc

Voltage regulator time constant (Tc). Typical Value = 1.

◆ thetap

IEC61970::Base::Domain::AngleDegrees IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::thetap

Potential circuit phase angle (thetap). Typical Value = 20.

◆ tm

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::tm

Forward time constant of inner loop field regulator (Tm). Typical Value = 1.

◆ vbmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::vbmax

Maximum excitation voltage (Vbmax). Typical Value = 8.63.

◆ vgmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::vgmax

Maximum inner loop feedback voltage (Vgmax). Typical Value = 6.53.

◆ vimax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::vimax

Maximum voltage regulator input limit (Vimax). Typical Value = 0.2.

◆ vimin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::vimin

Minimum voltage regulator input limit (Vimin). Typical Value = -0.2.

◆ vrmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::vrmax

Maximum voltage regulator output (Vrmax). Typical Value = 1.

◆ vrmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::vrmin

Minimum voltage regulator output (Vrmin). Typical Value = 0.

◆ xl

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcST3A::xl

Reactance associated with potential source (Xl). Typical Value = 0.09.