#include <ExcPIC.h>
Proportional/Integral Regulator Excitation System Model. This model can be used to represent excitation systems with a proportional-integral (PI) voltage regulator controller.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::e1 |
Field voltage value 1 (E1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::e2 |
Field voltage value 2 (E2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::efdmax |
Exciter maximum limit (Efdmax). Typical Value = 8.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::efdmin |
Exciter minimum limit (Efdmin). Typical Value = -0.87.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ka |
PI controller gain (Ka). Typical Value = 3.15.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::kc |
Exciter regulation factor (Kc). Typical Value = 0.08.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ke |
Exciter constant (Ke). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::kf |
Rate feedback gain (Kf). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ki |
Current source gain (Ki). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::kp |
Potential source gain (Kp). Typical Value = 6.5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::se1 |
Saturation factor at E1 (Se1). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::se2 |
Saturation factor at E2 (Se2). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ta1 |
PI controller time constant (Ta1). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ta2 |
Voltage regulator time constant (Ta2). Typical Value = 0.01.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ta3 |
Lead time constant (Ta3). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::ta4 |
Lag time constant (Ta4). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::te |
Exciter time constant (Te). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::tf1 |
Rate feedback time constant (Tf1). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::tf2 |
Rate feedback lag time constant (Tf2). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::vr1 |
PI maximum limit (Vr1). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::vr2 |
PI minimum limit (Vr2). Typical Value = -0.87.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::vrmax |
Voltage regulator maximum limit (Vrmax). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcPIC::vrmin |
Voltage regulator minimum limit (Vrmin). Typical Value = -0.87.