IEC61970 16v29a
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B Class Reference

#include <ExcIEEEST5B.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU kc
 
IEC61970::Base::Domain::PU kr
 
IEC61970::Base::Domain::Seconds t1
 
IEC61970::Base::Domain::Seconds tb1
 
IEC61970::Base::Domain::Seconds tb2
 
IEC61970::Base::Domain::Seconds tc1
 
IEC61970::Base::Domain::Seconds tc2
 
IEC61970::Base::Domain::Seconds tob1
 
IEC61970::Base::Domain::Seconds tob2
 
IEC61970::Base::Domain::Seconds toc1
 
IEC61970::Base::Domain::Seconds toc2
 
IEC61970::Base::Domain::Seconds tub1
 
IEC61970::Base::Domain::Seconds tub2
 
IEC61970::Base::Domain::Seconds tuc1
 
IEC61970::Base::Domain::Seconds tuc2
 
IEC61970::Base::Domain::PU vrmax
 
IEC61970::Base::Domain::PU vrmin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

The class represents IEEE Std 421.5-2005 type ST5B model. The Type ST5B excitation system is a variation of the Type ST1A model, with alternative overexcitation and underexcitation inputs and additional limits.

Reference: IEEE Standard 421.5-2005 Section 7.5.

Note: the block diagram in the IEEE 421.5 standard has input signal Vc and does not indicate the summation point with Vref. The implementation of the ExcIEEEST5B shall consider summation point with Vref.

Member Data Documentation

◆ kc

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::kc

Rectifier regulation factor (KC). Typical Value = 0.004.

◆ kr

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::kr

Regulator gain (KR). Typical Value = 200.

◆ t1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::t1

Firing circuit time constant (T1). Typical Value = 0.004.

◆ tb1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tb1

Regulator lag time constant (TB1). Typical Value = 6.

◆ tb2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tb2

Regulator lag time constant (TB2). Typical Value = 0.01.

◆ tc1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tc1

Regulator lead time constant (TC1). Typical Value = 0.8.

◆ tc2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tc2

Regulator lead time constant (TC2). Typical Value = 0.08.

◆ tob1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tob1

OEL lag time constant (TOB1). Typical Value = 2.

◆ tob2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tob2

OEL lag time constant (TOB2). Typical Value = 0.08.

◆ toc1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::toc1

OEL lead time constant (TOC1). Typical Value = 0.1.

◆ toc2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::toc2

OEL lead time constant (TOC2). Typical Value = 0.08.

◆ tub1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tub1

UEL lag time constant (TUB1). Typical Value = 10.

◆ tub2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tub2

UEL lag time constant (TUB2). Typical Value = 0.05.

◆ tuc1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tuc1

UEL lead time constant (TUC1). Typical Value = 2.

◆ tuc2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::tuc2

UEL lead time constant (TUC2). Typical Value = 0.1.

◆ vrmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::vrmax

Maximum voltage regulator output (VRMAX). Typical Value = 5.

◆ vrmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcIEEEST5B::vrmin

Minimum voltage regulator output (VRMIN). Typical Value = -4.