IEC61970::Base::Domain::PU edfmax
 
IEC61970::Base::Domain::PU efd1
 
IEC61970::Base::Domain::PU efd2
 
IEC61970::Base::Domain::Boolean efdlim
 
IEC61970::Base::Domain::PU efdmin
 
IEC61970::Base::Domain::Boolean exclim
 
IEC61970::Base::Domain::PU ke
 
IEC61970::Base::Domain::PU kr
 
IEC61970::Base::Domain::PU ks
 
IEC61970::Base::Domain::PU kv
 
IEC61970::Base::Domain::Float seefd1
 
IEC61970::Base::Domain::Float seefd2
 
IEC61970::Base::Domain::Seconds te
 
IEC61970::Base::Domain::Seconds trh
 
IEC61970::Base::Domain::PU vrmax
 
IEC61970::Base::Domain::PU vrmin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

This is modified IEEE DC3A direct current commutator exciters with speed input, and death band. DC old type 4.

Member Data Documentation

◆ edfmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::edfmax

Maximum voltage exciter output limiter (Efdmax). Typical Value = 99.

◆ efd1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efd1

Exciter voltage at which exciter saturation is defined (Efd1). Typical Value = 2.6.

◆ efd2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efd2

Exciter voltage at which exciter saturation is defined (Efd2). Typical Value = 3.45.

◆ efdlim

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efdlim

(Efdlim). true = exciter output limiter is active false = exciter output limiter not active. Typical Value = true.

◆ efdmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::efdmin

Minimum voltage exciter output limiter (Efdmin). Typical Value = -99.

◆ exclim

IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::exclim

(exclim). IEEE standard is ambiguous about lower limit on exciter output. true = a lower limit of zero is applied to integrator output false = a lower limit of zero not applied to integrator output. Typical Value = true.

◆ ke

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::ke

Exciter constant related to self-excited field (Ke). Typical Value = 1.

◆ kr

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::kr

Death band (Kr). If Kr is not zero, the voltage regulator input changes at a constant rate if Verr > Kr or Verr < -Kr as per the IEEE (1968) Type 4 model. If Kr is zero, the error signal drives the voltage regulator continuously as per the IEEE (1980) DC3 and IEEE (1992, 2005) DC3A models. Typical Value = 0.

◆ ks

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::ks

Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0.

◆ kv

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::kv

Fast raise/lower contact setting (Kv). Typical Value = 0.05.

◆ seefd1

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::seefd1

Exciter saturation function value at the corresponding exciter voltage, Efd1 (Se[Eefd1]). Typical Value = 0.1.

◆ seefd2

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::seefd2

Exciter saturation function value at the corresponding exciter voltage, Efd2 (Se[Efd2]). Typical Value = 0.35.

◆ te

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::te

Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 1.83.

◆ trh

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::trh

Rheostat travel time (Trh). Typical Value = 20.

◆ vrmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::vrmax

Maximum voltage regulator output (Vrmax). Typical Value = 5.

◆ vrmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcDC3A::vrmin

Minimum voltage regulator output (Vrmin). Typical Value = 0.