#include <ExcBBC.h>
Transformer fed static excitation system (static with ABB regulator). This model represents a static excitation system in which a gated thyristor bridge fed by a transformer at the main generator terminals feeds the main generator directly.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::efdmax |
Maximum open circuit exciter voltage (Efdmax). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::efdmin |
Minimum open circuit exciter voltage (Efdmin). Typical Value = -5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::k |
Steady state gain (K). Typical Value = 300.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::routing_selector |
Supplementary signal routing selector (switch). true = Vs connected to 3rd summing point false = Vs connected to 1st summing point (see diagram). Typical Value = true.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::t1 |
Controller time constant (T1). Typical Value = 6.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::t2 |
Controller time constant (T2). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::t3 |
Lead/lag time constant (T3). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::t4 |
Lead/lag time constant (T4). Typical Value = 0.01.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::vrmax |
Maximum control element output (Vrmax). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::vrmin |
Minimum control element output (Vrmin). Typical Value = -5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcBBC::xe |
Effective excitation transformer reactance (Xe). Typical Value = 0.05.