IEC61970 16v29a
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7 Class Reference

#include <ExcAVR7.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU a1
 
IEC61970::Base::Domain::PU a2
 
IEC61970::Base::Domain::PU a3
 
IEC61970::Base::Domain::PU a4
 
IEC61970::Base::Domain::PU a5
 
IEC61970::Base::Domain::PU a6
 
IEC61970::Base::Domain::PU k1
 
IEC61970::Base::Domain::PU k3
 
IEC61970::Base::Domain::PU k5
 
IEC61970::Base::Domain::Seconds t1
 
IEC61970::Base::Domain::Seconds t2
 
IEC61970::Base::Domain::Seconds t3
 
IEC61970::Base::Domain::Seconds t4
 
IEC61970::Base::Domain::Seconds t5
 
IEC61970::Base::Domain::Seconds t6
 
IEC61970::Base::Domain::PU vmax1
 
IEC61970::Base::Domain::PU vmax3
 
IEC61970::Base::Domain::PU vmax5
 
IEC61970::Base::Domain::PU vmin1
 
IEC61970::Base::Domain::PU vmin3
 
IEC61970::Base::Domain::PU vmin5
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

IVO excitation system.

Member Data Documentation

◆ a1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::a1

Lead coefficient (A1). Typical Value = 0.5.

◆ a2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::a2

Lag coefficient (A2). Typical Value = 0.5.

◆ a3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::a3

Lead coefficient (A3). Typical Value = 0.5.

◆ a4

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::a4

Lag coefficient (A4). Typical Value = 0.5.

◆ a5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::a5

Lead coefficient (A5). Typical Value = 0.5.

◆ a6

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::a6

Lag coefficient (A6). Typical Value = 0.5.

◆ k1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::k1

Gain (K1). Typical Value = 1.

◆ k3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::k3

Gain (K3). Typical Value = 3.

◆ k5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::k5

Gain (K5). Typical Value = 1.

◆ t1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::t1

Lead time constant (T1). Typical Value = 0.05.

◆ t2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::t2

Lag time constant (T2). Typical Value = 0.1.

◆ t3

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::t3

Lead time constant (T3). Typical Value = 0.1.

◆ t4

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::t4

Lag time constant (T4). Typical Value = 0.1.

◆ t5

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::t5

Lead time constant (T5). Typical Value = 0.1.

◆ t6

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::t6

Lag time constant (T6). Typical Value = 0.1.

◆ vmax1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::vmax1

Lead-lag max. limit (Vmax1). Typical Value = 5.

◆ vmax3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::vmax3

Lead-lag max. limit (Vmax3). Typical Value = 5.

◆ vmax5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::vmax5

Lead-lag max. limit (Vmax5). Typical Value = 5.

◆ vmin1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::vmin1

Lead-lag min. limit (Vmin1). Typical Value = -5.

◆ vmin3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::vmin3

Lead-lag min. limit (Vmin3). Typical Value = -5.

◆ vmin5

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR7::vmin5

Lead-lag min. limit (Vmin5). Typical Value = -2.


The documentation for this class was generated from the following files: