#include <ExcAVR1.h>
Italian excitation system corresponding to IEEE (1968) Type 1 Model. It represents exciter dynamo and electromechanical regulator.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::e1 |
Field voltage value 1 (E1). Typical Value = 4.18.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::e2 |
Field voltage value 2 (E2). Typical Value = 3.14.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::ka |
AVR gain (KA). Typical Value = 500.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::kf |
Rate feedback gain (KF). Typical Value = 0.12.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::se1 |
Saturation factor at E1 (S(E1)). Typical Value = 0.1.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::se2 |
Saturation factor at E2 (S(E2)). Typical Value = 0.03.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::ta |
AVR time constant (TA). Typical Value = 0.2.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::tb |
AVR time constant (TB). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::te |
Exciter time constant (TE). Typical Value = 1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::tf |
Rate feedback time constant (TF). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::vrmn |
Minimum AVR output (VRMN). Typical Value = -6.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR1::vrmx |
Maximum AVR output (VRMX). Typical Value = 7.