Italian excitation system. It represents static field voltage or excitation current feedback excitation system.
IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::blint |
Governor Control Flag (BLINT). 0 = lead-lag regulator 1 = proportional integral regulator. Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::ifmn |
Minimum exciter current (IFMN). Typical Value = -5.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::ifmx |
Maximum exciter current (IFMX). Typical Value = 6.5.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::k2 |
Exciter gain (K2). Typical Value = 20.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::k3 |
AVR gain (K3). Typical Value = 1000.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::kce |
Ceiling factor (KCE). Typical Value = 1.
IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::krvecc |
Feedback enabling (KRVECC). 0 = Open loop control 1 = Closed loop control. Typical Value = 1.
IEC61970::Base::Domain::Integer IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::kvfif |
Rate feedback signal flag (KVFIF). 0 = output voltage of the exciter 1 = exciter field current. Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::t1 |
Time constant (T1). Typical Value = 20.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::t2 |
Time constant (T2). Typical Value = 0.05.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::t3 |
Time constant (T3). Typical Value = 1.6.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::tb |
Exciter time constant (TB). Typical Value = 0.04.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::vrmn |
Minimum AVR output (VRMN). Typical Value = -5.2.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcANS::vrmx |
Maximum AVR output (VRMX). Typical Value = 6.5.