#include <ExcAC8B.h>
Modified IEEE AC8B alternator-supplied rectifier excitation system with speed input and input limiter.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::inlim |
Input limiter indicator. true = input limiter Vimax and Vimin is considered false = input limiter Vimax and Vimin is not considered. Typical Value = true.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::ka |
Voltage regulator gain (Ka). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::kc |
Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 0.55.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::kd |
Demagnetizing factor, a function of exciter alternator reactances (Kd). Typical Value = 1.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::kdr |
Voltage regulator derivative gain (Kdr). Typical Value = 10.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::ke |
Exciter constant related to self-excited field (Ke). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::kir |
Voltage regulator integral gain (Kir). Typical Value = 5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::kpr |
Voltage regulator proportional gain (Kpr). Typical Value = 80.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::ks |
Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::pidlim |
PID limiter indicator. true = input limiter Vpidmax and Vpidmin is considered false = input limiter Vpidmax and Vpidmin is not considered. Typical Value = true.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::seve1 |
Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]). Typical Value = 0.3.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::seve2 |
Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]). Typical Value = 3.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::ta |
Voltage regulator time constant (Ta). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::tdr |
Lag time constant (Tdr). Typical Value = 0.1.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::te |
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 1.2.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::telim |
Selector for the limiter on the block [1/sTe]. See diagram for meaning of true and false. Typical Value = false.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::ve1 |
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1) equals VEMAX (Ve1). Typical Value = 6.5.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::ve2 |
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2). Typical Value = 9.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vemin |
Minimum exciter voltage output (Vemin). Typical Value = 0.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vfemax |
Exciter field current limit reference (Vfemax). Typical Value = 6.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vimax |
Input signal maximum (Vimax). Typical Value = 35.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vimin |
Input signal minimum (Vimin). Typical Value = -10.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vpidmax |
PID maximum controller output (Vpidmax). Typical Value = 35.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vpidmin |
PID minimum controller output (Vpidmin). Typical Value = -10.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vrmax |
Maximum voltage regulator output (Vrmax). Typical Value = 35.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vrmin |
Minimum voltage regulator output (Vrmin). Typical Value = 0.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC8B::vtmult |
Multiply by generator's terminal voltage indicator. true =the limits Vrmax and Vrmin are multiplied by the generator’s terminal voltage to represent a thyristor power stage fed from the generator terminals false = limits are not multiplied by generator's terminal voltage. Typical Value = false.