#include <ExcAC2A.h>
Modified IEEE AC2A alternator-supplied rectifier excitation system with different field current limit.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::hvgate |
Indicates if HV gate is active (HVgate). true = gate is used false = gate is not used. Typical Value = true.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::ka |
Voltage regulator gain (Ka). Typical Value = 400.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kb |
Second stage regulator gain (Kb) (>0). Exciter field current controller gain. Typical Value = 25.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kb1 |
Second stage regulator gain (Kb1). It is exciter field current controller gain used as alternative to Kb to represent a variant of the ExcAC2A model. Typical Value = 25.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kc |
Rectifier loading factor proportional to commutating reactance (Kc). Typical Value = 0.28.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kd |
Demagnetizing factor, a function of exciter alternator reactances (Kd). Typical Value = 0.35.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::ke |
Exciter constant related to self-excited field (Ke). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kf |
Excitation control system stabilizer gains (Kf). Typical Value = 0.03.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kh |
Exciter field current feedback gain (Kh). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kl |
Exciter field current limiter gain (Kl). Typical Value = 10.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::kl1 |
Coefficient to allow different usage of the model (Kl1). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::ks |
Coefficient to allow different usage of the model-speed coefficient (Ks). Typical Value = 0.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::lvgate |
Indicates if LV gate is active (LVgate). true = gate is used false = gate is not used. Typical Value = true.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::seve1 |
Exciter saturation function value at the corresponding exciter voltage, Ve1, back of commutating reactance (Se[Ve1]). Typical Value = 0.037.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::seve2 |
Exciter saturation function value at the corresponding exciter voltage, Ve2, back of commutating reactance (Se[Ve2]). Typical Value = 0.012.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::ta |
Voltage regulator time constant (Ta). Typical Value = 0.02.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::tb |
Voltage regulator time constant (Tb). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::tc |
Voltage regulator time constant (Tc). Typical Value = 0.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::te |
Exciter time constant, integration rate associated with exciter control (Te). Typical Value = 0.6.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::tf |
Excitation control system stabilizer time constant (Tf). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::vamax |
Maximum voltage regulator output (Vamax). Typical Value = 8.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::vamin |
Minimum voltage regulator output (Vamin). Typical Value = -8.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::ve1 |
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve1). Typical Value = 4.4.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::ve2 |
Exciter alternator output voltages back of commutating reactance at which saturation is defined (Ve2). Typical Value = 3.3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::vfemax |
Exciter field current limit reference (Vfemax). Typical Value = 4.4.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::vlr |
Maximum exciter field current (Vlr). Typical Value = 4.4.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::vrmax |
Maximum voltage regulator outputs (Vrmax). Typical Value = 105.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAC2A::vrmin |
Minimum voltage regulator outputs (Vrmin). Typical Value = -95.