#include <ExternalNetworkInjection.h>
This class represents external network and it is used for IEC 60909 calculations.
IEC61970::Base::Domain::ActivePowerPerFrequency IEC61970::Base::Wires::ExternalNetworkInjection::governorSCD |
Power Frequency Bias. This is the change in power injection divided by the change in frequency and negated. A positive value of the power frequency bias provides additional power injection upon a drop in frequency.
IEC61970::Base::Domain::Boolean IEC61970::Base::Wires::ExternalNetworkInjection::ikSecond |
Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik").
IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::ExternalNetworkInjection::maxInitialSymShCCurrent |
Maximum initial symmetrical short-circuit currents (Ik" max) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::ExternalNetworkInjection::maxP |
Maximum active power of the injection.
IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::ExternalNetworkInjection::maxQ |
Not for short circuit modelling; It is used for modelling of infeed for load flow exchange. If maxQ and minQ are not used ReactiveCapabilityCurve can be used
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::maxR0ToX0Ratio |
Maximum ratio of zero sequence resistance of Network Feeder to its zero sequence reactance (R(0)/X(0) max). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::maxR1ToX1Ratio |
Maximum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) max). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::maxZ0ToZ1Ratio |
Maximum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) max). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::CurrentFlow IEC61970::Base::Wires::ExternalNetworkInjection::minInitialSymShCCurrent |
Minimum initial symmetrical short-circuit currents (Ik" min) in A (Ik" = Sk"/(SQRT(3) Un)). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::ExternalNetworkInjection::minP |
Minimum active power of the injection.
IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::ExternalNetworkInjection::minQ |
Not for short circuit modelling; It is used for modelling of infeed for load flow exchange. If maxQ and minQ are not used ReactiveCapabilityCurve can be used
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::minR0ToX0Ratio |
Indicates whether initial symmetrical short-circuit current and power have been calculated according to IEC (Ik"). Used for short circuit data exchange according to IEC 6090
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::minR1ToX1Ratio |
Minimum ratio of positive sequence resistance of Network Feeder to its positive sequence reactance (R(1)/X(1) min). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::Float IEC61970::Base::Wires::ExternalNetworkInjection::minZ0ToZ1Ratio |
Minimum ratio of zero sequence impedance to its positive sequence impedance (Z(0)/Z(1) min). Used for short circuit data exchange according to IEC 60909
IEC61970::Base::Domain::ActivePower IEC61970::Base::Wires::ExternalNetworkInjection::p |
Active power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.
IEC61970::Base::Domain::ReactivePower IEC61970::Base::Wires::ExternalNetworkInjection::q |
Reactive power injection. Load sign convention is used, i.e. positive sign means flow out from a node. Starting value for steady state solutions.
IEC61970::Base::Domain::Integer IEC61970::Base::Wires::ExternalNetworkInjection::referencePriority |
Priority of unit for use as powerflow voltage phase angle reference bus selection. 0 = don t care (default) 1 = highest priority. 2 is less than 1 and so on.
IEC61970::Base::Domain::PU IEC61970::Base::Wires::ExternalNetworkInjection::voltageFactor |
Voltage factor in pu, which was used to calculate short-circuit current Ik" and power Sk".