CIM++ Adapted CIM Codebase
|
#include <WindContPType3IEC.h>
P control model Type 3.
Reference: IEC Standard 61400-27-1 Section 6.6.5.3.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dpmax |
Maximum wind turbine power ramp rate (dpmax). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::dtrisemaxlvrt |
Limitation of torque rise rate during LVRT for S1 (dTrisemaxLVRT). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kdtd |
Gain for active drive train damping (KDTD). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kip |
PI controller integration parameter (KIp). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::kpp |
PI controller proportional gain (KPp). It is type dependent parameter.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::mplvrt |
Enable LVRT power control mode (MpLVRT). true = 1: voltage control false = 0: reactive power control.
It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::omegaoffset |
Offset to reference value that limits controller action during rotor speed changes (omegaoffset). It is case dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::pdtdmax |
Maximum active drive train damping power (pDTDmax). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::rramp |
Ramp limitation of torque, required in some grid codes (Rramp). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tdvs |
Time delay after deep voltage sags (TDVS). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::temin |
Minimum electrical generator torque (Temin). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tomegafilt |
Filter time constant for generator speed measurement (Tomegafilt). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tpfilt |
Filter time constant for power measurement (Tpfilt). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tpord |
Time constant in power order lag (Tpord). It is type dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tufilt |
Filter time constant for voltage measurement (Tufilt). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::tuscale |
Voltage scaling factor of reset-torque (Tuscale). It is project dependent parameter.
IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::twref |
Time constant in speed reference filter (Tomega,ref). It is type dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::udvs |
Voltage limit for hold LVRT status after deep voltage sags (uDVS). It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::updip |
Voltage dip threshold for P-control (uPdip). Part of turbine control, often different (e.g 0.8) from converter thresholds. It is project dependent parameter.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::wdtd |
Active drive train damping frequency (omegaDTD). It can be calculated from two mass model parameters. It is type dependent parameter.
IEC61970::Dynamics::StandardModels::WindDynamics::WindGenTurbineType3IEC* IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::WindGenTurbineType3IEC |
Wind turbine type 3 model with which this Wind control P type 3 model is associated.
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::WindDynamics::WindContPType3IEC::zeta |
Coefficient for active drive train damping (zeta). It is type dependent parameter.