IEC61970 16v29a - SINERGIEN 20170705
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID Class Reference

#include <GovHydroWPID.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU d
 
IEC61970::Base::Domain::PU gatmax
 
IEC61970::Base::Domain::PU gatmin
 
IEC61970::Base::Domain::PU gv1
 
IEC61970::Base::Domain::PU gv2
 
IEC61970::Base::Domain::PU gv3
 
IEC61970::Base::Domain::PU kd
 
IEC61970::Base::Domain::PU ki
 
IEC61970::Base::Domain::PU kp
 
IEC61970::Base::Domain::ActivePower mwbase
 
IEC61970::Base::Domain::PU pgv1
 
IEC61970::Base::Domain::PU pgv2
 
IEC61970::Base::Domain::PU pgv3
 
IEC61970::Base::Domain::PU pmax
 
IEC61970::Base::Domain::PU pmin
 
IEC61970::Base::Domain::PU reg
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tb
 
IEC61970::Base::Domain::Seconds treg
 
IEC61970::Base::Domain::Seconds tw
 
IEC61970::Base::Domain::PU velmax
 
IEC61970::Base::Domain::PU velmin
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::TurbineGovernorDynamics
IEC61970::Dynamics::StandardModels::AsynchronousMachineDynamics::AsynchronousMachineDynamicsAsynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Woodward PID Hydro Governor.

Member Data Documentation

◆ d

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::d

Turbine damping factor (D). Unit = delta P / delta speed.

◆ gatmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gatmax

Gate opening Limit Maximum (Gatmax).

◆ gatmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gatmin

Gate opening Limit Minimum (Gatmin).

◆ gv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gv1

Gate position 1 (Gv1).

◆ gv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gv2

Gate position 2 (Gv2).

◆ gv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::gv3

Gate position 3 (Gv3).

◆ kd

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::kd

Derivative gain (Kd). Typical Value = 1.11.

◆ ki

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::ki

Reset gain (Ki). Typical Value = 0.36.

◆ kp

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::kp

Proportional gain (Kp). Typical Value = 0.1.

◆ mwbase

IEC61970::Base::Domain::ActivePower IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::mwbase

Base for power values (MWbase) (>0). Unit = MW.

◆ pgv1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pgv1

Output at Gv1 PU of MWbase (Pgv1).

◆ pgv2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pgv2

Output at Gv2 PU of MWbase (Pgv2).

◆ pgv3

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pgv3

Output at Gv3 PU of MWbase (Pgv3).

◆ pmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pmax

Maximum Power Output (Pmax).

◆ pmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::pmin

Minimum Power Output (Pmin).

◆ reg

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::reg

Permanent drop (Reg).

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::ta

Controller time constant (Ta) (>0). Typical Value = 0.

◆ tb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::tb

Gate servo time constant (Tb) (>0). Typical Value = 0.

◆ treg

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::treg

Speed detector time constant (Treg).

◆ tw

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::tw

Water inertia time constant (Tw) (>0). Typical Value = 0.

◆ velmax

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::velmax

Maximum gate opening velocity (Velmax). Unit = PU/sec. Typical Value = 0.

◆ velmin

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::TurbineGovernorDynamics::GovHydroWPID::velmin

Maximum gate closing velocity (Velmin). Unit = PU/sec. Typical Value = 0.


The documentation for this class was generated from the following files: