IEC61970 16v29a - SINERGIEN 20170705
Public Attributes | List of all members
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2 Class Reference

#include <ExcAVR2.h>

Inheritance diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2:
Inheritance graph
[legend]
Collaboration diagram for IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2:
Collaboration graph
[legend]

Public Attributes

IEC61970::Base::Domain::PU e1
 
IEC61970::Base::Domain::PU e2
 
IEC61970::Base::Domain::Float ka
 
IEC61970::Base::Domain::Float kf
 
IEC61970::Base::Domain::Float se1
 
IEC61970::Base::Domain::Float se2
 
IEC61970::Base::Domain::Seconds ta
 
IEC61970::Base::Domain::Seconds tb
 
IEC61970::Base::Domain::Seconds te
 
IEC61970::Base::Domain::Seconds tf1
 
IEC61970::Base::Domain::Seconds tf2
 
IEC61970::Base::Domain::PU vrmn
 
IEC61970::Base::Domain::PU vrmx
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics
IEC61970::Dynamics::StandardModels::SynchronousMachineDynamics::SynchronousMachineDynamicsSynchronousMachineDynamics
 
- Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock
IEC61970::Base::Domain::Boolean enabled
 
- Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject
IEC61970::Base::Domain::String aliasName
 
IEC61970::Base::Domain::String description
 
IEC61970::Base::Domain::String mRID
 
IEC61970::Base::Domain::String name
 
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > DiagramObjects
 

Detailed Description

Italian excitation system corresponding to IEEE (1968) Type 2 Model. It represents alternator and rotating diodes and electromechanic voltage regulators.

Member Data Documentation

◆ e1

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::e1

Field voltage value 1 (E1). Typical Value = 4.18.

◆ e2

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::e2

Field voltage value 2 (E2). Typical Value = 3.14.

◆ ka

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::ka

AVR gain (KA). Typical Value = 500.

◆ kf

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::kf

Rate feedback gain (KF). Typical Value = 0.12.

◆ se1

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::se1

Saturation factor at E1 (S(E1)). Typical Value = 0.1.

◆ se2

IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::se2

Saturation factor at E2 (S(E2)). Typical Value = 0.03.

◆ ta

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::ta

AVR time constant (TA). Typical Value = 0.02.

◆ tb

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::tb

AVR time constant (TB). Typical Value = 0.

◆ te

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::te

Exciter time constant (TE). Typical Value = 1.

◆ tf1

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::tf1

Rate feedback time constant (TF1). Typical Value = 1.

◆ tf2

IEC61970::Base::Domain::Seconds IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::tf2

Rate feedback time constant (TF2). Typical Value = 1.

◆ vrmn

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::vrmn

Minimum AVR output (VRMN). Typical Value = -6.

◆ vrmx

IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcAVR2::vrmx

Maximum AVR output (VRMX). Typical Value = 7.


The documentation for this class was generated from the following files: