CIM++ Adapted CIM_SINERGIEN Codebase
|
#include <PFVArType2IEEEPFController.h>
Public Attributes | |
IEC61970::Base::Domain::Boolean | exlon |
IEC61970::Base::Domain::PU | ki |
IEC61970::Base::Domain::PU | kp |
IEC61970::Base::Domain::PU | pfref |
IEC61970::Base::Domain::PU | vclmt |
IEC61970::Base::Domain::PU | vref |
IEC61970::Base::Domain::Float | vs |
Public Attributes inherited from IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArControllerType2Dynamics | |
IEC61970::Dynamics::StandardModels::ExcitationSystemDynamics::ExcitationSystemDynamics * | ExcitationSystemDynamics |
Public Attributes inherited from IEC61970::Dynamics::StandardModels::DynamicsFunctionBlock | |
IEC61970::Base::Domain::Boolean | enabled |
Public Attributes inherited from IEC61970::Base::Core::IdentifiedObject | |
IEC61970::Base::Domain::String | aliasName |
IEC61970::Base::Domain::String | description |
IEC61970::Base::Domain::String | mRID |
IEC61970::Base::Domain::String | name |
std::list< IEC61970::Base::DiagramLayout::DiagramObject * > | DiagramObjects |
The class represents IEEE PF Controller Type 2 which is a summing point type controller and makes up the outside loop of a two-loop system. This controller is implemented as a slow PI type controller. The voltage regulator forms the inner loop and is implemented as a fast controller.
Reference: IEEE Standard 421.5-2005 Section 11.4.
IEC61970::Base::Domain::Boolean IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::exlon |
Overexcitation or under excitation flag (EXLON) true = 1 (not in the overexcitation or underexcitation state, integral action is active) false = 0 (in the overexcitation or underexcitation state, so integral action is disabled to allow the limiter to play its role).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::ki |
Integral gain of the pf controller (KI). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::kp |
Proportional gain of the pf controller (KP). Typical Value = 1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::pfref |
Power factor reference (PFREF).
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::vclmt |
Maximum output of the pf controller (VCLMT). Typical Value = 0.1.
IEC61970::Base::Domain::PU IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::vref |
Voltage regulator reference (VREF).
IEC61970::Base::Domain::Float IEC61970::Dynamics::StandardModels::PFVArControllerType2Dynamics::PFVArType2IEEEPFController::vs |
Generator sensing voltage (VS).